NIH POLICY MANUAL 1361 - Corridor Utilization 1. Explanation of Material Transmitted: This manual establishes the NIH policy for the safe use of corridors in buildings located on the NIH Bethesda reservation and at the NIH Animal Center (NIHAC) in Poolesville, Maryland. The chapter is revised to comply with the NIH Manual 5-year update policy and to reflect an organizational change in oversight responsibility from the Division of Occupational Health and Safety to the Division of the Fire Marshal. 2. Filing Instructions:
* Note: Section A was revised 3/4/08 to remove the italicized text below and add the bolded text below. Previous Section A: Established under this chapter is the NIH policy for the safe use of corridors in buildings located on the NIH Bethesda reservation, the Rocky Mountain Laboratory (RML) in Hamilton, MT and at the NIH Animal Center (NIHAC) in Poolesville, MD. This policy is not intended to apply to main building entrances/lobbies that are not integral to the building's egress corridors or atriums of any building as other fire protection and life safety criteria provide the requirements for the furnishings and finishes of these spaces. Revised Section A: Established under this chapter is the NIH policy for the safe use of corridors, as well as alcoves and elevator lobbies that are open to egress corridor systems, in buildings located on the NIH Bethesda reservation, the Rocky Mountain Laboratory (RML) in Hamilton, MT and at the NIH Animal Center (NIHAC) in Poolesville, MD. This policy is not intended to apply to main building entrances/lobbies or atriums of any building. PLEASE NOTE: For information on:
Established under this chapter is the NIH policy for the safe use of corridors, as well as alcoves and elevator lobbies that are open to egress corridor systems, in buildings located on the NIH Bethesda reservation, the Rocky Mountain Laboratory (RML) in Hamilton, MT and at the NIH Animal Center (NIHAC) in Poolesville, MD. This policy is not intended to apply to main building entrances/lobbies or atriums of any building. The NIH Corridor Utilization Policy applies only to buildings located on the NIH Bethesda reservation, the RML, and the NIHAC in Poolesville and is based on the judgment that certain uses for the corridor, in addition to the safe movement of people, can be accommodated without compromising the safe and adequate means of egress. It is the policy of the NIH that all corridors of buildings located on the Bethesda reservation, the RML and at the NIHAC provide for: (1) a readily apparent, safe and adequate means by which building occupants may exit a building in the event of a fire or other serious emergency; (2) adequate access and use by emergency personnel; (3) the safe movement of people during normal daily use of the building; and (4) the safe transportation of goods and materials. The NIH Corridor Utilization Policy (Appendix 1) details specific allowances, restrictions and requirements for corridor use. Buildings constructed or renovated after 1991 shall be designed with clear and unobstructed corridors. Corridor storage shall not be permitted in these buildings. Limited storage of items in the corridors of existing buildings shall be allowed only as defined by the NIH Corridor Utilization Policy (Appendix 1). All corridors and safe areas designated for patient care and treatment in Building 10 shall meet the standards as outlined by the Joint Commission on Accreditation of Health Care Organizations. Health care standards for fire safety are more restrictive than those for public areas and laboratories because corridors and exits must accommodate patients, many of whom are incapable of self-preservation in the event of an emergency. In buildings permitted to have corridor storage, elevator lobbies shall be subject to the requirements and restrictions of Appendix 1, however these areas will also have to be evaluated by the Division of the Fire Marshal, Office of Research Services (DFM/ORS) to consider reasonable allowances to evacuate personnel with physical disabilities at passenger elevator lobbies and the movement of materials from freight elevator lobbies. Buildings occupied by NIH employees, which are located outside the Bethesda, NIHAC and RML sites, shall conform to the requirements of the local authority having jurisdiction. For further information, contact the NIH, Division of the Fire Marshal, Office of Research Services (DFM/ORS) at (301) 496-0487. E. Records Retention and Disposal: All records (e-mail and non-e-mail) pertaining to this chapter must be retained and
disposed of under the authority of NIH Manual 1743,
"Keeping and Destroying Records, Appendix 1, NIH Records Control Schedule,"
Item 1300, Station Management. The purpose of this manual issuance is to provide guidance to NIH personnel for the safe use of corridors in buildings located on the NIH Bethesda reservation, the RML in Hamilton, MT and at the NIHAC in Poolesville, MD. 1. Office Responsible for Reviewing Management Controls Relative to this Chapter (Issuing Office): Through this manual issuance, the Division of the Fire Marshal (DFM) is accountable for the method used to ensure that management controls are implemented and working. 2. Frequency of Review (in years): The NIH Corridor Utilization Policy is reviewed annually and updated as needed by the DFM. 3. Method of Review: 4. Review Reports are sent to: the Deputy Director for Management and the Deputy Director for Intramural Research. Reports should indicate that controls are in place and working well or indicate any management control issues that should be brought to the attention of the report recipient (s). This policy represents the combined effort of the NIH Fire Marshal, NIH management, the Division of Occupational Health and Safety and the occupants of various NIH buildings. Requirements for providing safe and adequate means of egress have been balanced with routine building use needs and the continuing shortage of space. The degree to which this policy successfully achieves such a balance may be seen differently by various groups; in all probability it will not be seen as totally satisfying to any group. However, adherence to these provisions will provide for an acceptable level of safety to building occupants and emergency and service personnel, while still accommodating utilization of the corridors for specific purposes. Fire codes and building regulations establish requirements for safe and adequate means of egress from buildings during emergencies. A fundamental principle of these codes and regulations is to maintain exit paths (i.e., corridors) which are free of obstructions and hazards. The NIH policy is based on the judgment that certain uses for the corridor, in addition to the safe movement of people, can be accommodated without compromising the safe and adequate means of egress. In order to assist building occupants and those responsible for the implementation of this policy, explanatory comments are provided in the right hand column, adjacent to the policy. The policy is printed in the left hand column in bold type. Appendix 1 - NIH Corridor Utilization Policy Purpose: C. The Division of the Fire Marshal/ORS is responsible for providing additional guidance or interpretation of the provisions of this policy; conducting periodic inspections of NIH corridors for the purpose of advising each IC of conditions requiring corrective action and taking immediate action by notifying the appropriate IC Lead Administrative Officer with copies to the Scientific Director and Executive Officer to bring about the removal of items that would prevent safe egress of building occupants. The minimum corridor width prescribed below shall be maintained: A. Corridors required for emergency evacuation in patient care areas of Building 10 and the Clinical Center (CC) shall be at least eight feet in clear and unobstructed width. Patient-use corridors in the ACRF shall be clear and unobstructed the full constructed width. This requirement for corridors in patient care areas is specifically stated in both the National Fire Protection Association's Life Safety Code (NFPA 101) and the Joint Commission on Accreditation of Healthcare Organizations (JCAHO) Standards. It is based on the need to provide for the transport of patients in beds, litters or similar equipment. The restriction is not intended to prohibit the temporary parking of small wheeled carts or similar mobile equipment required for patient care which would not impede evacuation. Corridor widths in the ACRF are subject to a different section of the applicable codes and meet the necessary minimum widths as constructed. The NIH Fire Marshal must approve all temporary exceptions to these provisions and measures to compensate for diminished life safety. As in 1.A above, this requirement is not intended to prohibit the temporary parking of an occasional laboratory cart which may be quickly moved by the occupants in order to provide full access. Locations for such equipment shall be provided on the side of the corridor authorized for equipment or storage (see Section
3.D). Storage is not permitted in the 200 Corridor of the ACRF. This Policy prohibits the use of the clear width for temporary storage of construction material, equipment scheduled for installation, supplies pending movement into labs or offices, surplus materials or similar items which would jeopardize area occupants. C. A minimum 54 inch width of clear and unobstructed egress must be maintained in all corridors of other buildings. No exceptions to reduce the corridor width from the stated dimensions shall be permitted. D. Corridors of buildings located outside the Bethesda/RML/NIHAC sites shall conform to the requirements of the local Authority Having Jurisdiction. From a practical standpoint, this prohibits the use of the corridor for any storage and/or operation of equipment. For example, Montgomery County Fire Codes require that corridors be kept clear from wall-to-wall regardless of width. NIH is not in a position to grant exceptions to this requirement. "Marshalling Areas" are intended to serve as locations for controlled evacuation of personnel. At NIH they are provided in Buildings 10, ACRF and Lister Hill. In patient care area marshalling or “Safe” areas designated for staging patients during an evacuation include the atrium and elevator lobbies on the east and west end of each patient care unit, respectively, in the Building 10 Complex. In addition, the East, West and Center elevator lobbies are considered as marshalling areas for the evacuation of the non-patient care areas of Building 10. In addition to providing a level of fire protection similar to stairwells or horizontal exits, such areas are also equipped with automatic mechanical means to prevent smoke from entering the area. The NIH Fire Marshal must approve all temporary exceptions to the provisions for patient safe areas in Building 10 and measures to compensate for diminished level of life safety. 3. Allowances, Restrictions and Requirements for Corridor Use. Per Section C above the use of corridors for storage is prohibited in buildings constructed or those that have undergone major renovations after 1993. See comments under Requirements 1.A and 1.B above. This practice is generally intended to permit storage and/or operation of certain equipment on the side of the corridor opposite the stairwell door to ensure that, under emergency conditions, there will be no impediments to reaching the stairwell. However, in some corridors, utility modifications have resulted in enclosed chases projecting from the side of the corridor normally preferred as the "clear" side. Where this condition exists, utilization is limited to the side with the projecting utility chases. In buildings where access to a stairwell or horizontal exit is in the end wall of the corridor, the primary or lead Institute/Center shall establish which side will be used for materials or equipment. The selected side shall be uniform throughout the building to enable the occupants to become familiar with a clear path pattern regardless of the floor they occupy at the time of an emergency. This uniformity will also allow the Division of Emergency Preparedness and Coordination (DEPC), to plan emergency response patterns. C. Such use does not involve the storage or use of: o Flammable or combustible liquids (except as noted). Failure to adhere to these provisions may compromise the NIH license to use radionuclides issued by the U. S. Nuclear Regulatory Commission. Users found in violation of these provisions are subject to temporary or permanent loss of their authority to use radionuclides. Further information is available in the NIH Radiation Safety Guide and from the Division of Radiation Safety (DRS), (301) 496-5774. o Biological agents at or above Biosafety Level 2 or those requiring BSL2 or higher physical containment. Refrigerators or freezers containing only non-restricted material do not present any unique hazards and are permitted. However, the user should consider the potential risk associated with the material stored, the frequency of access (regular and frequent access increases the probability of accidental breakage) and the consequences of electrical or equipment failure (e.g., internal temperature rise resulting in vapor overpressure, exothermic reaction, etc.). Equipment designed to operate under either positive or negative pressure shall be located in the laboratory. There is a clear risk of pressure-related explosions or implosions in addition to the risks that may be associated with the agents or compounds used in such equipment. At NIH, there have been several instances where the cover of a lyophilizer has fractured under normal operations and a lyophilizer was the source of a serious fire loss. Incubators, used in compliance with this Section, are permitted in corridors since their normal operating temperatures do not pose undue risks. However, drying ovens, which operate at far higher temperatures, are not permitted in the corridor. Other types of equipment not permitted in corridors are those utilizing high voltage (e.g., some equipment used for electrophoresis) or those posing mechanical hazards such as unguarded belts, pulleys or gears. Normally, duplicating or copy machines which do not utilize flammable liquids are permitted, provided that excess paper stock is not stored in the open corridor. o Electrically powered coffee pots are prohibited in corridors. Coffee Pots produce heat and are often sources of ignition of fires. To protect the means of egress these appliances should be located in a break room or similar area which is separated from the corridor by walls and a door. o Live Animals. o Construction Materials. All furniture shall be constructed of noncombustible or factory-applied fire retardant treated materials. This requirement also permits storage in standard file cabinets and similar metal furnishings. Storage on top of cabinets is not allowed in order to eliminate potential injury from material or equipment that may become accidentally dislodged. Combustible materials (e.g., paper, wood, plastic or similar materials) are to be stored within the cabinets, since they constitute a fuel source which would serve to spread fire through the corridor. Combustible furniture and cabinets can also serve as a fuel source and shall not be stored or used in the corridor. Glass-fronted refrigerators having impact resistant tempered glass doors shall be permitted.
The requirement for metal doors is intended to eliminate the risk of personal injury should someone fall against a glass door. Refrigerators having glass doors are permitted to be located in a corridor provided that the manufacturer certifies in writing that the glass tempered. The Joint Commission on Accreditation of Health Care Organizations restricts the type and quantity of compressed gas that may be stored in health care areas. Clinical Center policies stipulate the requirements for use and storage of gas cylinders in the hospital. 5. Local Policies and Restrictions An IC may establish additional requirements for the space it occupies in a building as provided in this Section. |